46 CFR 25.30-10: Portable fire extinguishers and semi-portable systems
Last reviewed: November 9, 2026
This section covers how portable and semi-portable extinguishers must be inspected, maintained and located. They must follow NFPA 10, and the owner or managing operator must give the marine inspector evidence of servicing. It also restricts certain extinguisher types and sets rules for older dry chemical units.
What it says
Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10, which is incorporated by reference (see § 25.01-3).
46 CFR 25.30-10(a)“Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10”
The owner, operator, person-in-charge, or a designated member of the crew may conduct the monthly inspections that NFPA 10 requires.
46 CFR 25.30-10(c)“Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew.”
The owner or managing operator must give the marine inspector satisfactory evidence of the required servicing.
46 CFR 25.30-10(e)“The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector.”
If any of the equipment or records has not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests.
46 CFR 25.30-10(e)“If any of the equipment or records has not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests.”
Vaporizing-liquid type fire extinguishers containing carbon tetrachloride, chlorobromomethane, or other toxic vaporizing liquids are not acceptable as equipment required by this subchapter.
46 CFR 25.30-10(f)“Vaporizing-liquid type fire extinguishers containing carbon tetrachloride, chlorobromomethane, or other toxic vaporizing liquids are not acceptable as equipment required by this subchapter.”
Portable or semi-portable extinguishers that their name plates require to be protected from freezing must not be located where freezing temperatures may be expected.
46 CFR 25.30-10(g)“must not be located where freezing temperatures may be expected.”
Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all portions of the space concerned may be covered.
46 CFR 25.30-10(j)“Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all portions of the space concerned may be covered.”
Common questions
Who can do the annual maintenance on non-rechargeable extinguishers?
The annual maintenance need not be done by a certified person. The owner, operator, person-in-charge, or a designated member of the crew can do it.
“the annual maintenance need not be conducted by a certified person and can be conducted by the owner, operator, person-in-charge, or a designated member of the crew.”
Does a servicing tag count as proof of maintenance?
A tag issued by a qualified servicing organization and attached to each extinguisher may be accepted as evidence that the necessary maintenance procedures have been conducted.
“A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted.”
Will the Coast Guard accept state or local servicing agency certification?
Yes. Certification or licensing by a state or local jurisdiction as a fire extinguisher servicing agency will be accepted as meeting the NFPA 10 personnel certification requirements for annual maintenance and recharging of extinguishers.
“Certification or licensing by a state or local jurisdiction as a fire extinguisher servicing agency will be accepted by the Coast Guard as meeting the personnel certification requirements of NFPA 10”
The text of 46 CFR 25.30-10
Electronic Code of Federal Regulations (eCFR), current as of March 31, 2026 · Read it on eCFR
Portable fire extinguishers and semi-portable fire extinguishing systems
(a) Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10 (incorporated by reference, see § 25.01-3).
(b) Certification or licensing by a state or local jurisdiction as a fire extinguisher servicing agency will be accepted by the Coast Guard as meeting the personnel certification requirements of NFPA 10 for annual maintenance and recharging of extinguishers.
(c) Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew.
(d) Non-rechargeable or non-refillable extinguishers must be inspected and maintained in accordance with NFPA 10; however, the annual maintenance need not be conducted by a certified person and can be conducted by the owner, operator, person-in-charge, or a designated member of the crew.
(e) The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records has not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests. A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted.
(f) Vaporizing-liquid type fire extinguishers containing carbon tetrachloride, chlorobromomethane, or other toxic vaporizing liquids are not acceptable as equipment required by this subchapter.
(g) Portable or semi-portable extinguishers, which are required on their name plates to be protected from freezing, must not be located where freezing temperatures may be expected.
(h) The use of dry chemical, stored pressure, fire extinguishers not fitted with pressure gauges or indicating devices, manufactured prior to January 1, 1965, may be permitted on motorboats and other vessels so long as such extinguishers are maintained in good and serviceable condition. The following maintenance and inspections are required for such extinguishers:
(1) When the date on the inspection record tag on the extinguishers shows that 6 months have elapsed since the last weight check ashore, then such extinguishers are no longer accepted as meeting required maintenance conditions until they are reweighed ashore, found to be in a serviceable condition, and within required weight conditions.
(2) If the weight of the container is 1/4 ounce less than that stamped on the container, it must be serviced.
(3) If the outer seal or seals (which indicate tampering or use when broken) are not intact, the boarding officer or marine inspector will inspect such extinguishers to see that the frangible disc in the neck of the container is intact; and if such disc is not intact, the container must be serviced.
(4) If there is evidence of damage, use, or leakage, such as dry chemical powder observed in the nozzle or elsewhere on the extinguisher, the extinguisher must be serviced or replaced.
(i) Dry chemical extinguishers, stored pressure extinguishers, and fire extinguishers without pressure gauges or indicating devices manufactured after January 1, 1965, cannot be labeled with the marine type label described in 46 CFR 162.028-4. These extinguishers manufactured after January 1, 1965, may be carried onboard motorboats or other vessels as excess equipment.
(j) Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all portions of the space concerned may be covered.
Sections it refers to
The plain-English explanation on this page was written with AI from the regulation text above and checked automatically before publishing: every quote appears in the text, every number comes from it, and a second model confirmed each statement adds nothing the text doesn't say. Regulation text current as of March 31, 2026. The regulation text governs. RegKnot is not affiliated with the U.S. Coast Guard.