46 CFR 95.10-5: Fire pump requirements for vessels

Last reviewed: October 14, 2026

This section requires vessels to have independently driven fire pumps in accordance with Table 95.10-5(a). It also sets rules for pump capacity, pressure, relief valves, pressure gages, use for other purposes, piping and pump location.

Applies toVessels that must be equipped with independently driven fire pumps under Table 95.10-5(a).

What it says

  1. Vessels must have independently driven fire pumps as set out in Table 95.10-5(a).

    46 CFR 95.10-5(a)“Vessels must be equipped with independently driven fire pumps in accordance with Table 95.10-5(a).”
  2. Each pump must be able to deliver water at the same time from the two highest outlets at a Pitot tube pressure of approximately 50 p.s.i.

    46 CFR 95.10-5(c)“Each pump must be capable of delivering water simultaneously from the two highest outlets at a Pitot tube pressure of approximately 50 p.s.i.”
  3. Where 3/4-inch hose is permitted by Table 95.10-5(a), the Pitot tube pressure need be only 35 p.s.i.

    46 CFR 95.10-5(c)“Where 3/4-inch hose is permitted by Table 95.10-5(a), the Pitot tube pressure need be only 35 p.s.i.”
  4. Fire pumps must have relief valves on the discharge side. They are set to relieve at 25 p.s.i. above the pressure needed to meet paragraph (c), or at 125 p.s.i., whichever is greater.

    46 CFR 95.10-5(d)“Fire pumps must be fitted on the discharge side with relief valves set to relieve at 25 p.s.i. in excess of the pressure necessary to maintain the requirements of paragraph (c) of this section or 125 p.s.i., whichever is greater.”
  5. Fire pumps must have a pressure gage on the discharge side of the pumps.

    46 CFR 95.10-5(e)“Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.”
  6. Fire pumps may be used for other purposes if at least one required pump is kept available for the fire system at all times. A pump connected to an oil line shall never be used as a fire pump.

    46 CFR 95.10-5(f)“Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times.”
  7. The total area of the pipes leading from a pump must not be less than the discharge area of the pump.

    46 CFR 95.10-5(g)“The total area of the pipes leading from a pump must not be less than the discharge area of the pump.”

Common questions

Can a fire pump be used for other purposes?

Yes, if at least one of the required pumps is kept available for the fire system at all times. A pump connected to an oil line shall not be used as a fire pump.

“Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times.”

Does a fire pump need a pressure gage?

Yes. Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.

“Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.”

Can relief valves on fire pumps be omitted?

Relief valves may be omitted if the pumps, operating under shut-off conditions, are not capable of developing a pressure exceeding the relief setting in paragraph (d).

“Relief valves may be omitted if the pumps, operating under shut-off conditions, are not capable of developing a pressure exceeding this amount.”

The text of 46 CFR 95.10-5

Electronic Code of Federal Regulations (eCFR), current as of March 31, 2026 · Read it on eCFR

Fire pumps

(a) Vessels must be equipped with independently driven fire pumps in accordance with Table 95.10-5(a).

Table 95.10-5(a)—Fire Pump System Requirements Gross tons Minimumnumber ofpumps Hose andhydrantsize, inches Nozzle orifice size, inches Length of hose, feet Over Not over 100 1 1 1 11⁄2 1 1⁄2 1 50 100 1,000 1 1 1⁄2 5⁄8 50 1,000 1,500 2 1 1⁄2 5⁄8 50 1,500 2 2 21⁄2 2 7⁄8 2 50 1 On vessels of 65 feet (19.8 meters) in length or less, 3⁄4-inch hose of a good commercial grade together with a commercial garden hose nozzle may be used. The pump may be hand operated and the length of hose must be sufficient to assure coverage of all parts of the vessel. 2 A 11⁄2 inch hose that is 75 feet (22.86 meters) in length with a 5⁄8-inch nozzle may be used where specified by § 95.10-10(b) of this subpart for interior locations and 50 feet (15.24 meters) of 11⁄2 inch hose may be used in exterior locations on vessels in other than ocean or coastwise service. For vessels on ocean or coastwise service, two 11⁄2 inch outlets, each provided with one 11⁄2 inch hose supplied through a wye connection may be substituted.

(b) On vessels of 1,000 gross tons or more on an international voyage, each required fire pump, while delivering water thru the fire main system at a pressure corresponding to that required by paragraph (c) of this section, must have a minimum capacity of at least two-thirds of that required for an independent bilge pump. However, in no case may the capacity of each fire pump be less than that otherwise required by this section.

(c) Each pump must be capable of delivering water simultaneously from the two highest outlets at a Pitot tube pressure of approximately 50 p.s.i. Where 1 1/2-inch hose is permitted in lieu of 2 1/2-inch hose by footnote 2 of Table 95.10-5(a), the pump capacity must be determined on the same basis as if 2 1/2-inch hose had been permitted. Where 3/4-inch hose is permitted by Table 95.10-5(a), the Pitot tube pressure need be only 35 p.s.i.

(d) Fire pumps must be fitted on the discharge side with relief valves set to relieve at 25 p.s.i. in excess of the pressure necessary to maintain the requirements of paragraph (c) of this section or 125 p.s.i., whichever is greater. Relief valves may be omitted if the pumps, operating under shut-off conditions, are not capable of developing a pressure exceeding this amount.

(e) Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.

(f) Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times. In no case shall a pump having connection to an oil line be used as a fire pump. Branch lines connected to the fire main for purposes other than fire and deck wash shall be so arranged that adequate water can be made continuously available for firefighting purposes.

(g) The total area of the pipes leading from a pump must not be less than the discharge area of the pump.

(h) On vessels with oil fired boilers, either main or auxiliary, or with internal combustion propulsion machinery, where two fire pumps are required, they shall be located in separate spaces, and the arrangement of pumps, sea connections, and sources of power shall be such as to insure that a fire in any one space will not put all of the fire pumps out of operation. However, when it is shown to the satisfaction of the Commandant that it is unreasonable or impracticable to meet this requirement due to the size or arrangement of the vessel, or for other reasons, the installation of a total flooding fixed fire extinguishing or clean agent system may be accepted as an alternate method of extinguishing any fire that could affect the powering and operation of at least one of the required fire pumps.

Sections it refers to

The plain-English explanation on this page was written with AI from the regulation text above and checked automatically before publishing: every quote appears in the text, every number comes from it, and a second model confirmed each statement adds nothing the text doesn't say. Regulation text current as of March 31, 2026. The regulation text governs. RegKnot is not affiliated with the U.S. Coast Guard.