46 CFR 193.10-5: Fire pumps on vessels
Last reviewed: October 14, 2026
This section requires vessels to carry independently driven fire pumps as set out in Table 193.10-5(a). It also covers pump pressure, relief valves, pressure gages, other uses of pumps, pump location, and keeping hose streams immediately available from the fire main.
Applies toVessels that must be equipped with independently driven fire pumps under Table 193.10-5(a).
What it says
Vessels must be equipped with independently driven fire pumps in accordance with Table 193.10-5(a).
46 CFR 193.10-5(a)“Vessels must be equipped with independently driven fire pumps in accordance with Table 193.10-5(a) of this section.”
Where 3/4-inch hose is permitted by Table 193.10-5(a), the Pitot tube pressure may not be less than 35 p.s.i.
46 CFR 193.10-5(c)“Where 3/4-inch hose is permitted by Table 193.10-5(a), the Pitot tube pressure may not be less than 35 p.s.i.”
Fire pumps must have a pressure gage on the discharge side of the pumps.
46 CFR 193.10-5(e)“Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.”
Fire pumps may be used for other purposes if at least one of the required pumps is kept available for use on the fire system at all times.
46 CFR 193.10-5(f)“Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times.”
A pump having connection to an oil line may never be used as a fire pump.
46 CFR 193.10-5(f)“In no case may a pump having connection to an oil line be used as a fire pump.”
Where two fire pumps are required on vessels with main or auxiliary oil-fired boilers or with internal combustion propulsion machinery, the pumps must be located in separate spaces. The Commandant may accept a fixed fire extinguishing system as an alternate if meeting this is shown to be unreasonable or impracticable.
46 CFR 193.10-5(h)“the pumps must be located in separate spaces.”
Except as provided for in § 193.10-10(e), a sufficient number of hose streams must be immediately available from the fire main at all times, by maintaining water pressure or by remote control of fire pumps.
46 CFR 193.10-5(i)“a sufficient number of hose streams for fire fighting purposes must be immediately available from the fire main at all times”
Common questions
What is the minimum pressure when 3/4-inch hose is permitted?
Where Table 193.10-5(a) permits 3/4-inch hose, the Pitot tube pressure may not be less than 35 p.s.i.
“Where 3/4-inch hose is permitted by Table 193.10-5(a), the Pitot tube pressure may not be less than 35 p.s.i.”
Can a fire pump be used for other purposes?
Yes. Fire pumps may be used for other purposes if at least one of the required pumps is kept available for use on the fire system at all times.
“Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times.”
Do fire pumps need a pressure gage?
Yes. Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.
“Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.”
Can relief valves be omitted on fire pumps?
Yes, if the pumps, operating under shutoff conditions, are not capable of developing a pressure exceeding the relief setting amount.
“Relief valves may be omitted if the pumps, operating under shutoff conditions, are not capable of developing a pressure exceeding this amount.”
The text of 46 CFR 193.10-5
Electronic Code of Federal Regulations (eCFR), current as of March 31, 2026 · Read it on eCFR
Fire pumps
(a) Vessels must be equipped with independently driven fire pumps in accordance with Table 193.10-5(a) of this section.
Table 193.10-5(a)—Required Fire Pump System Gross tons Minimumnumber ofpumps Hose andhydrant size, inches Nozzle orifice size, inches Length of hose, feet Over Not over 100 1 1 1 1 1⁄2 1 1⁄2 50 100 1,000 1 11⁄2 5⁄8 50 1,000 1,500 2 11⁄2 5⁄8 50 1,500 2 2 21⁄2 2 7⁄8 2 50 1 On vessels of 65 feet (19.8 meters) in length or less, 3⁄4 inch hose of good commercial grade together with a commercial garden hose nozzle may be used. The pump may be hand operated and the length of hose must be sufficient to assure coverage of all parts of the vessel. 2 75 feet (22.86 meters) of 11⁄2 inch hose and 5⁄8 inch nozzle may be used where specified by § 193.10-10(b) for interior locations and 50 feet (15.24 meters) of 11⁄2 inch hose may be used in exterior locations on vessels in other than ocean or coastwise services. Vessels on ocean or coastwise services may substitute two 11⁄2 inch outlets with two 11⁄2 inch hoses supplied through a wye connection in exterior locations.
(b) On vessels of 1,000 gross tons or more on an international voyage, each required fire pump, while delivering water through the fire main system at a pressure corresponding to that required by paragraph (c) of this section, must have a minimum capacity of at least two-thirds of that required for an independent bilge pump. However, in no case shall the capacity of each fire pump be less than that otherwise required by this section.
(c) Each pump must be capable of delivering water simultaneously from the outlets having the greatest pressure drop from the fire pumps to the nozzles which may not always be the two highest outlets, at a Pitot tube pressure of not less than 50 p.s.i. Where 1 1/2-inch hose is permitted in lieu of 2 1/2-inch hose by footnote 2 of Table 193.10-5(a), the pump capacity must be determined on the same basis as if 2 1/2-inch hose had been permitted. Where 3/4-inch hose is permitted by Table 193.10-5(a), the Pitot tube pressure may not be less than 35 p.s.i.
(d) Fire pumps must be fitted on the discharge side with relief valves set to relieve at 25 p.s.i. in excess of the pressure necessary to maintain the requirements of paragraph (c) of this section or 125 p.s.i., whichever is greater. Relief valves may be omitted if the pumps, operating under shutoff conditions, are not capable of developing a pressure exceeding this amount.
(e) Fire pumps must be fitted with a pressure gage on the discharge side of the pumps.
(f) Fire pumps may be used for other purposes provided at least one of the required pumps is kept available for use on the fire system at all times. In no case may a pump having connection to an oil line be used as a fire pump. Branch lines connected to the fire main for purposes other than fire and deck wash must be so arranged that adequate water can be made continuously available for firefighting purposes.
(g) The total area of the pipes leading from a pump must not be less than the discharge area of the pump.
(h) Where two fire pumps are required on vessels with main or auxiliary oil-fired boilers or with internal combustion propulsion machinery, the pumps must be located in separate spaces. The pumps, sea connections, and sources of power must be arranged to ensure that a fire in any one space will not put all of the fire pumps out of operation. However, where it is shown to the satisfaction of the Commandant that it is unreasonable or impracticable to meet this requirement, the installation of a fixed fire extinguishing system may be accepted as an alternate method of extinguishing any fire that would affect the powering and operation for the required fire pumps.
(i) Except as provided for in § 193.10-10(e), a sufficient number of hose streams for fire fighting purposes must be immediately available from the fire main at all times by either of the following methods:
(1) Maintenance of water pressure. (i) Water pressure must be maintained on the fire main at all times by the continuous operation of:
(A) One of the fire pumps; or
(B) Another suitable pump capable of supplying one hose stream at a Pitot tube pressure of not less than 50 p.s.i. (35 p.s.i. for 3/4-inch hose); or,
(C) A pressure tank capable of supplying one hose stream at a Pitot tube pressure of not less than 50 p.s.i. (35 p.s.i. for 3/4-inch hose) for five minutes.
(ii) An audible alarm must be installed to sound in a continuously manned space if the pressure in the fire main drops to less than that necessary to maintain the minimum Pitot tube pressures specified in § 193.10-5(i)(1)(i)(B).
(2) Remote control of fire pumps. (i) At least one fire pump must be capable of remote activation and control.
(ii) If the fire pump is in a continuously manned machinery space, the controls for operating it and the controls for all necessary valves must be located on the manned operating platform in that space.
(iii) If the fire pump is in an unmanned machinery space, the controls for its operation and the controls for all necessary valves must be located in:
(A) The fire control station, if any; or,
(B) The bridge, if there is no fire control station; or,
(C) A readily accessible space acceptable to the Officer in Charge, Marine Inspection.
Sections it refers to
The plain-English explanation on this page was written with AI from the regulation text above and checked automatically before publishing: every quote appears in the text, every number comes from it, and a second model confirmed each statement adds nothing the text doesn't say. Regulation text current as of March 31, 2026. The regulation text governs. RegKnot is not affiliated with the U.S. Coast Guard.