46 CFR 142.330: Fire-detection system requirements for towing vessels

Last reviewed: October 14, 2026

This section sets fire-detection requirements for towing vessels. Each towing vessel must have a system to detect engine room fires, with an exception for certain older vessels. It also requires smoke detection in berthing spaces and lounges, and heat detection in the galley of each new towing vessel with a galley.

Applies toTowing vessels, with the galley heat-detection requirement applying to each new towing vessel equipped with a galley.

What it says

  1. Except as provided in paragraph (a)(8), each towing vessel must have a fire-detection system installed to detect engine room fires.

    46 CFR 142.330(a)“each towing vessel must have a fire-detection system installed to detect engine room fires.”
  2. The owner or managing operator must ensure that each detector, control panel, remote indicator panel, and fire alarm is approved by the Commandant under approval series 161.002 or listed by a NRTL as set forth in 29 CFR 1910.7.

    46 CFR 142.330(a)(1)“Each detector, control panel, remote indicator panel, and fire alarm are approved by the Commandant under approval series 161.002 or listed by a NRTL as set forth in 29 CFR 1910.7;”
  3. The system must be arranged and installed so that an engine room fire automatically sets off alarms on a fire detection control panel at the operating station.

    46 CFR 142.330(a)(3)“The system is arranged and installed so a fire in the engine room automatically sets off alarms on a fire detection control panel at the operating station.”
  4. The system must draw power from two sources, and switchover from the primary source to the secondary source may be manual or automatic.

    46 CFR 142.330(a)(5)“The system draws power from two sources. Switchover from the primary source to the secondary source may be either manual or automatic;”
  5. A towing vessel whose construction was contracted for before January 18, 2000, may use an existing engine room monitoring system with fire-detection capability instead, if it is operable, complies with paragraphs (a)(2) through (7), and uses detectors listed by an NRTL.

    46 CFR 142.330(a)(8)“may use an existing engine room monitoring system (with fire-detection capability) instead of a fire-detection system, if the monitoring system is operable”
  6. Each towing vessel must have a means to detect smoke in the berthing spaces and lounges that alerts individuals in those spaces.

    46 CFR 142.330(b)“Each towing vessel must be equipped with a means to detect smoke in the berthing spaces and lounges that alerts individuals in those spaces.”
  7. Smoke detection systems or individual detectors must be kept operational at all times when the crew is onboard the towing vessel.

    46 CFR 142.330(b)“Detection systems or individual detectors must be kept operational at all times when the crew is onboard the towing vessel.”
  8. Each new towing vessel equipped with a galley must have a heat-detection system with one or more restorable heat-sensing detectors to detect galley fires.

    46 CFR 142.330(c)“Each new towing vessel equipped with a galley must have a heat-detection system with one or more restorable heat-sensing detectors to detect fires in the galley.”

Common questions

Can battery-operated smoke detectors be used in towing vessel berthing spaces?

Yes. Smoke detection may be an installed detection system or individual battery-operated detectors meeting UL 217.

“or by using individual battery-operated detectors meeting UL 217 (incorporated by reference, see § 136.112 of this subchapter).”

Does a towing vessel need a fire control panel at every operating station?

No. On vessels with more than one operating station, only one must have a fire detection control panel. Any other operating station must have either a fire detection control panel or a remote indicator panel.

“On vessels with more than one operating station, only one of them must be outfitted with a fire detection control panel.”

Where must the galley heat-detection alarm sound?

The galley heat-detection system must be arranged to sound an audible alarm at each operating station.

“The system must be arranged to sound an audible alarm at each operating station.”

Who must certify the design and installation of a towing vessel fire-detection system?

A registered professional engineer with experience in fire-detection system design, a NICET level IV fire alarm engineering technician, or an authorized classification society with equivalent experience must certify and inspect it.

“is certified and inspected by a registered professional engineer with experience in fire-detection system design”

The text of 46 CFR 142.330

Electronic Code of Federal Regulations (eCFR), current as of April 16, 2026 · Read it on eCFR

Fire-detection system requirements

(a) Fire-detection systems. Except as provided in paragraph (a)(8) of this section, each towing vessel must have a fire-detection system installed to detect engine room fires. The owner or managing operator must ensure the following:

(1) Each detector, control panel, remote indicator panel, and fire alarm are approved by the Commandant under approval series 161.002 or listed by a NRTL as set forth in 29 CFR 1910.7;

(2) The system is installed, tested, and maintained in accordance with the manufacturer's design manual;

(3) The system is arranged and installed so a fire in the engine room automatically sets off alarms on a fire detection control panel at the operating station. On vessels with more than one operating station, only one of them must be outfitted with a fire detection control panel. Any other operating station must be outfitted with either a fire detection control panel or a remote indicator panel;

(4) The control panel includes:

(i) A power available light;

(ii) An audible to notify crew of a fire;

(iii) Visual alarm alarms to identify the zone or zones of origin of the fire;

(iv) A means to silence the audible alarm while maintaining indication by the visual alarms;

(v) A circuit-fault detector test-switch, or internal supervision of circuit integrity; and

(vi) Labels for all switches and indicator lights, identifying their functions.

(5) The system draws power from two sources. Switchover from the primary source to the secondary source may be either manual or automatic;

(6) The system serves no other purpose, unless it is an engine room monitoring system complying with paragraph (a)(8) of this section; and

(7) The design of the system and its installation on the towing vessel is certified and inspected by a registered professional engineer with experience in fire-detection system design, by a technician with qualifications as a National Institute for Certification in Engineering Technologies (NICET) level IV fire alarm engineering technician, or by an authorized classification society with equivalent experience, to comply with paragraphs (a)(1) through (6) of this section.

(8) A towing vessel whose construction was contracted for prior to January 18, 2000, may use an existing engine room monitoring system (with fire-detection capability) instead of a fire-detection system, if the monitoring system is operable and complies with paragraphs (a)(2) through (7) of this section, and uses detectors listed by an NRTL.

(b) Smoke detection in berthing spaces. Each towing vessel must be equipped with a means to detect smoke in the berthing spaces and lounges that alerts individuals in those spaces. This may be accomplished by an installed detection system, or by using individual battery-operated detectors meeting UL 217 (incorporated by reference, see § 136.112 of this subchapter). Detection systems or individual detectors must be kept operational at all times when the crew is onboard the towing vessel.

(c) Heat-detection system in galley. Each new towing vessel equipped with a galley must have a heat-detection system with one or more restorable heat-sensing detectors to detect fires in the galley. The system must be arranged to sound an audible alarm at each operating station. This may be a separate zone in the detection system required by paragraph (a) of this section, or a separate detection system complying with paragraphs (a)(1) and (2) of this section.

Sections it refers to

The plain-English explanation on this page was written with AI from the regulation text above and checked automatically before publishing: every quote appears in the text, every number comes from it, and a second model confirmed each statement adds nothing the text doesn't say. Regulation text current as of April 16, 2026. The regulation text governs. RegKnot is not affiliated with the U.S. Coast Guard.